Products

Adjustable ventilation opening, square, plastic - Extraction or supply - DN125

bouche-3049
14 Days
ManufacturerHelios OriginEurope Type of outletBlowing in, Suction, Adjustable
Description of the square adjustable supply or extraction vents The vents are in diameter 125 to adapt to the vent connection tees. Material: ABS thermoplastic polymer + elastomer gasket Colour: White RAL 9016 Maximum extraction rate: 50 m3/h at 3m/s Coanda effect and low induction...
36€00
Price (without VAT) = 30€00

7 days

Free delivery in France from 2400€ttc
Payment: 4x free of charge
Delivery method
  • Back to top
  • Description
  • Features
  • Customer reviews
Description

Description of the square adjustable supply or extraction vents

  • The vents are in diameter 125 to adapt to the vent connection tees.
  • Material: ABS thermoplastic polymer + elastomer gasket
  • Colour: White RAL 9016
  • Maximum extraction rate: 50 m3/h at 3m/s
  • Coanda effect and low induction mouth
  • Dimensions of the visible part: Height 15 to 30 mm x 176.5 mm x 176.5 mm

Advantages of square adjustable supply and extract valves

  • Adjustable airflow: optimization of airflows per room
  • Avoids the deposit of dust on the ceiling
  • Acoustic comfort
  • Possibility to insert a G2 filter

How to balance double flow ventilation flows?

There are generally two ways to balance the flow rates:
  1. With self-adjusting vents in the service rooms (WC, bathroom, other water rooms):
Flow rate calibrated at 15 m3/h or 30 m3/h and double flow rates in the kitchen. The other rooms are equipped with manually adjustable vents. Goal :
  • comply with the decree of March 24, 1982 on the minimum and maximum flow rates to be extracted from service rooms (see table above),
Advantages :
  • easier to balance,
  • maximum regulatory flow rate to be extracted in the kitchen is more easily reached.
Disadvantages:
  • self-adjusting valves require a pressure of at least 50 Pa to operate correctly,
Precaution:
  • it is necessary to check with the flowmeter or the pressure sensor the correct functioning of the vents.
  1. With manually adjustable vents in all rooms:
The opening of the mouths can be more or less closed according to the desired flow.
Advantages :
  • flexibility of flow rates and general over-ventilation of the building,
  • less network load losses.
Disadvantages:
  • balancing requiring equipment (flow meter) and specific methodology.
  • this solution generally offered by foreign manufacturers does not allow compliance with the order of March 1982 on the minimum and maximum flow rates to be extracted.